"America's advocate for the availability of clean, safe, well designed public restrooms"

 

            
Donations to the ARA are tax-exempt  under section 501(c)(3) of the Internal Revenue Code

 

 

 

NATIONAL MODEL COMPREHENSIVE
BUILDING TOILET CODE 
( Relating to public use of toilet facilities in business and mercantile establishments) 

 

 


!! RECENT ARA INFLUENCED CODE UPGRADES !!

Business and mercantile establishments occasionally indicate they have no customer toilet facilities.  Most likely the store managers, owners and even some local code officials are not aware that this policy is at variance with their municipalities building code.  The following  2009 International Plumbing Code Change will likely improve awareness that customer restrooms are a mandated

2007 IPC 403.5.1 Directional signage. Directional signage indicating the route to the public facilities shall be posted in accordance with Section 3107 of the IBC. Such signage shall be located in a corridor or aisle at the entrance to the facilities for customers and visitors. 

 

Toilet code enforcement ambiguity has  been addressed by the following change that was published in the  2009 International Property Maintenance Codes.

2009 IPC 502.5 Public toilet facilities. Public toilet facilities shall be maintained in a safe sanitary and working condition in accordance with the International Plumbing Code. Except for periodic maintenance or cleaning, public access and use shall be provided to the toilet facilities at all times during occupancy of the premises

 

Family/assisted-use toilets provide inherent potty parity. Two Family/assisted-use toilets increase overall availability. A single gender based toilet can be unavailable for periods of up to 15 minutes when, for example, the current occupant is using it for companion care, to change diapers, or to change a colostomy bag. Less need for gender based cleaning staff. Less impact when one toilet room is being cleaned or serviced. For decades, males and females have used the same toilet facility on airliners.

2012 IPC 403.2.1 (IBC [P]2902.2.1) Family or assisted-use toilet facilities serving as separate facilities. Where a building or tenant space requires a separate toilet facility for each sex and each toilet facility is required to have only one water closet, two family/assisted-use toilet facilities shall be permitted to serve as the required separate facilities. Family or assisted-use toilet facilities shall not be required to be identified for exclusive use by either sex as required by Section 403.4.

 

 

 

EXECUTIVE OVERVIEW

The majority of  States adopt comprehensive consensus code that contains well-vetted language, which requires toilets facilities for customers, patrons and visitors.  This code is typically mandated Statewide or where not mandated is often adopted voluntarily at the municipal level.  With a few exceptions States adopt either the International Plumbing Code (IPC), the Uniform Plumbing Code (UPC) or the National Standard Plumbing Code (NSPC). Provided below is non-authoritative overview of these codes and their applicability 

Note: The references below are for general information only.  Refer to source documents for official references.
Note:  Highlighting and some bold face are not in the source documents.

 

INDEX

Code Adoption by State  
Uniform Plumbing Code
 
UPC   UPC Clarification  
International Plumbing Code
IPC
National Standard Plumbing Code
NSPC 
Americans with Disabilities Act Accessibility Guidelines Guidelines
(ADAAG).
Older buildings
  

Gender [Potty] Parity Code Discussion  
Restroom Privacy Code Support  
Miscellaneous State Legislation

 

... The city's health and plumbing inspector, after conferring with the state's chief plumbing inspector, notified store employees and the supervisor that they were wrong in denying the woman access to the bathroom. City and state codes require that customers, patrons and visitors to such public businesses must be allowed to use toilet facilities. ... ... the state inspector, agreed, listing a series of state codes dating back to the late 1970s in addition to the 2000 edition of the International Plumbing Code, which the city adopted. ... ... a store that violates codes can be found guilty of a misdemeanor charge ...
Source:
Woman denied use of public restroom at Rochester thrift storeAdam Krauss  Staff Writer Foster Democrat 6/9/05 

_______________________________________________

... visited a Dollar Tree store and, while shopping, have asked to use the restroom. I was told that the urinal had been kicked over so they no longer let the public use the facilities. The second time I was told that their shipment was blocking the doorway...   ...I talked to a friend [different State] ... about my experience. ... Her local Dollar Tree wouldn't let her use the restroom because the "urinal had been kicked over". 
Source: ARA Feedback dtd 27 Sep 2006  19:07:02

_______________________________________________

SOME COMPANIES GO WITH THE CODE 
....There was a time when it used to cost a dime to use public bathrooms. But this retail establishment knew how to keep their shoppers happy: “FREE TOILETS” is spelled out in classic Art Deco typography... ...Excuse yourself for a visit here today....
Source: 'Lunchtime tourist' Linda Koutsky Downtown Journal, Minneapolis, MN 10/11/06 

 

 

 

STATE ADOPTION OF  MODEL CODE 
IPC - International Plumbing Code  UPC - Uniform Plumbing Code  NSP - National Standard Plumbing Code

Alabama		IPC adopted by Local Governments
Alaska		UPC adopted at State level but IPC in use locally
Arizona		UPC adopted at State level but IPC in use locally
Arkansas	State Plumbing Code
California	UPC applicable Statewide
Colorado	UPC adopted at State level but IPC in use locally
Connecticut	IPC effective Statewide
D.C.		IPC effective in city
Delaware	IPC effective Statewide
Florida		IPC effective Statewide
Georgia		IPC effective Statewide
Hawaii		UPC most of the Islands
Idaho		UPC effective Statewide
Illinois	Develops their own code
Illinois	IPC adopted by Local Governments
Indiana		UPC base document for State code
Iowa		IPC adopted by Local Governments
Iowa		UPC effective Statewide
Kansas		UPC adopted at State level but IPC in use locally
Kentucky 	State Plumbing Code based on IPC precursor
Louisiana	State Plumbing Code based on IPC precursor
Maine		IPC adopted by Local Governments
Maryland	NSP at State Level, some use of IPC locally
Massachusetts	Develops their own Uniform State Plumbing Code
Michigan	IPC effective Statewide
Minnesota	UPC effective Statewide(1)
Mississippi	IPC adopted by Local Governments
Missouri	TBD either IPC or UPC effective Statewide
Montana		UPC effective Statewide
Nebraska	UPC adopted at State level but IPC in use locally
Nevada		UPC adopted at State level but IPC in use locally
New Hampshire	IPC effective Statewide
New Jersey	NSP at State Level
New Mexico	UPC adopted at State level but IPC in use locally
New York	IPC effective Statewide
North Carolina	IPC effective Statewide
North Dakota	UPC effective Statewide
Ohio		IPC effective Statewide
Oklahoma	IPC effective Statewide
Oregon		UPC effective Statewide
Pennsylvania	IPC adopted, but may not yet be effective
Puerto Rico	IPC effective Statewide
Rhode Island	IPC effective Statewide
South Carolina	IPC effective Statewide
South Dakota	UPC 2003 version effective Statewide
Tennessee	IPC effective Statewide
Texas		IPC at State but Austin, Houston, San Antonio use UPC
US Virgin Is.	UPC Island wide
Utah		IPC effective Statewide
Vermont		Use 1990 BOCA (BOCA now under IPC)
Virginia	IPC effective Statewide
Wisconsin	Wisconsin UBC Ch 61-65
Washington	UPC effective Statewide
West Virginia	IPC effective Statewide
Wyoming		Both IPC & UPC used by Local Governments
International Plumbing Codes - Adoption by Jurisdiction provides a more current
and comprehensive listing

 

 

 

RESTROOM AVAILABILITY SUPPORT

TABLES FOR MINIMUM NUMBER OF TOILETS

International Plumbing Code           Mostly eastern States
Uniform Plumbing Code                 
Mostly western States
National Standard Plumbing Code  
Maryland & New Jersey
Illinois Plumbing Code                  
   Illinois does not adopt national code
New York City                                              NYC most likely will adopt IPC

Example of code modification process  
Submitting code recommendations
 
Submitting comment about the code

PROBLEMS WITH CODE ENFORCEMENT  and 

Maryland Public Restroom Law provides an example of State Legislator not being aware that their plumbing code already required toilets for customers in mercantile establishments

   

 

For information only please refer to official documents
 

2000 INTERNATIONAL PLUMBING CODE  (IPC)
Published by the 50,000-member organization  International Code Council (ICC), whose membership includes all voting members of BOCA, SBCCI, and ICBO (International Conference of Building Officials), the IPC incorporates much of the language of the BOCA National Plumbing Code and the SBCCA Standard Plumbing Code.

403.1 Minimum number of fixtures.  Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1*. Types of occupancies not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined the the International Code Council. Occupancy classification shall be determined in accordance with the International Code Council.   (*) Table 403.1 on this web site is an unofficial sample

403.1.1 Potty parity.  [Florida Modification] In assembly occupancies, restrooms which are open to the public must have a ratio of 3 to 2 water closets provided for women as the combined total of water closets and urinals provided for men, unless these are two or fewer such fixtures for men, 

403.6 Customer facilities.  Customers, patrons and visitors shall be provided with public toilet facilities in structures and tenant spaces intended for public utilization.  Public toilet facilities shall be located not more than one story above or below the space required to be provided with public toilet facilities and the path of travel to such facilities shall not exceed a distance of 500 feet (152 m).  

403.6.1  Covered malls.  In covered mall buildings, the path of travel to required toilet facilities shall not exceed a distance of 300 feet (91,440 mm).  The required facilities shall be based on total square footage, and facilities shall be installed in each individual store or in a central toilet area located in accordance with this section.  The maximum travel distance to the central toilet facilities in covered mall buildings shall be measured from the main entrance of any store or tenant space.
 
403.6.2 Pay facilities.  Required facilities shall be free of charge and designated by legible signs for each sex.  Where pay facilities are installed, such facilities shall be in excess of the required minimum facilities

____________________________________________________

Other relevant Code 

     

 

2003 UNIFORM PLUMBING CODE (UPC) Published by the International Association of Plumbing and Mechanical Officials   

413.2.2 Fixtures accessible only to private offices shall not be counted to determine compliance with this section. establishments with an occupant load of one hundred (100) or more shall be provided with separate facilities for employees and customers. Customer and employee facilities may be combined for occupant loads less than one hundred (100).

413.3 Separate Facilities
Separate toilet facilities shall be provided for each sex.
Exceptions:
(2) In occupancies serving ten (10) or fewer people, one (1) toilet facility, designed for use by no more than one (1) person at a time, shall be permitted for use by both sexes.
(3) In business and mercantile occupancies with a total floor area of fifteen hundred (1500) square feet (139.5 m 2 ) or less, one (1) toilet facility, designed for use by no more than one (1) person at a time, shall satisfy the requirements for serving customers and employees of both sexes.

413.5 Facilities in Mercantile and Business Occupancies Serving Customers
413.5.1 Requirements for customers and employees shall be permitted to be met with a single set of restrooms accessible to both groups. The required number of fixtures shall be the greater of the required number for employees or the required number for customers.
413.5.2 Fixtures for customer use shall be permitted to be met by providing a centrally located facility accessible to several stores. The maximum distance from entry to any store to this facility shall not exceed five hundred (500) feet (152.4 m).

Source:www.iapmo.org/common/ROP_UPC/PrePrint_UPC_2003/ preprint_ch4.pdf

_________________________________

 

Request for UPC Clarification

This is in response to your request for clarification on the Uniform Plumbing Code regarding facilities in mercantile/business occupancies, etc. The question(s) considered was (were):

Is it the intent of the 2003 UPC to require a toilet facility for customers, patrons, and visitors of all mercantile and business establishments?

The 2004 UPC Answers & Analysis Committee answered Item UPC #04-19 as follows:

Yes. The general provisions of Section 413.0 and Table 4-1 have requirements for employee use and public use in a number of occupancies including assembly, institutional, and office or public buildings.

Considering this issue were Chairman, John J. Roth, City of Houston, TX; Bob Adler, City of San Jose, CA; J. Trini Mendoza, County of Ventura, CA; Bruce Pfeiffer, City of Topeka, KS; Ed Schoenfeld, City of Salt Lake City, UT; G.F. ³Jed² Scheuermann, City of Portland, OR; and K. Anthony Wilcockson, City of Walnut Creek, CA. Thank you for your patience and interest in clarifying this matter.

Sincerely,
John J. Roth
Chairman, UPC Answers & Analysis Committee
-- 
By:
Johnni Brown
Answers & Analysis Committee Staff Liaison
IAPMO World Headquarters
5001 E Philadelphia Street
Ontario CA 91764-2816 USA
Telephone: (909) 472-4109
Facsimile: (909) 472-4157
Web Address: <http://www.iapmo.org>

 

   

 

2003 NATIONAL STANDARD PLUMBING CODE (NSPC)
Published by the Plumbing-Heating-Cooling Contractors--National Association 

7.21.4 Separate Facilities
Separate toilet facilities shall be provided for each sex.
EXCEPTIONS: 
[ deleted text ]

3. In businesses, occupancies with a total floor area of 1500 square feet or less, one toilet facility, de-signed for use by no more than one person at a time, shall satisfy the requirements for serving customers and employees of both sexes.
4. In mercantile occupancies with a net occupiable floor area of 1500 square feet or less that is accessible to customers, one toilet facility designed for use by no more than one person at a time, shall satisfy the requirements for serving customers and employees of both sexes.

7.21.7 Facilities in Mercantile and Business Occupancies Serving Customers
a. Requirements for customers and employees shall be permitted to be met with a single set of restrooms accessible to both groups. The required number of fixtures shall be the greater of the required number for employees or the required number for customers.
b. Fixtures for customer use shall be permitted to be met by providing a centrally located facility accessible to several stores. The maximum distance of entry from any store to this facility shall not exceed 500 feet.
c. In stores with a floor area of 150 square feet or less, the requirement to provide facilities for employees shall be permitted to be met by providing a centrally located facility accessible to several stores. The maximum distance of entry from any store to this facility shall not exceed 300 feet.
d. Drinking water facilities are not required for customers where normal occupancy is short term.
e. For establishments less than 1500 square feet in total floor area, one water closet and one lavatory in a restroom with a lockable door shall be permitted to provide the requirements for serving the customers and employees.

___________________________________________

Local Jurisdictions often strengthen the code requirements.  As an example some Jurisdition have amended the NSPC with the following amendment.

Amend Table 7.21.1."Minimum Number of Required Plumbing Fixtures: 
In item no. 7, "Mercantile," delete row (a) in its entirety and in the next row, in the "Description" after "Uses" insert

"All gasoline service stations shall provide toilet facilities to the public when open for business. There shall be separate facilities for men and women."

ARA Note: Using the above as an example,  to whom would one complain if not allowed to use the toilet facilities at a gasoline service station and what is the penalty?

 

EXAMPLES OF INDEPENDENT STATE CODE

 

ILLINOIS PLUMBING CODE 
SECTION 890.810 MINIMUM NUMBER OF PLUMBING FIXTURES 
Buildings with 5,000 square feet of gross public area or with occupancies of 100 or more persons shall provide public restrooms and drinking fountains as shown in Appendix A: Table B 

 

MASSACHUSETTS - UNIFORM STATE  PLUMBING CODE  
Scan to 
     (18) Minimum Facilities for Building Occupancy Other Than Residential
and to  
     Table 1: Minimum Facilities For Building Occupancy

248CMR Section 2.10
... Table: Minimum Facilities for Building Occupancy 

 


OLDER BUILDINGS

Older buildings are 'grand-fathered' as code is updated; that is an older building must abide by the applicable toilet codes at the time the build permit was issued.   Typically the older codes also contained an occupant base toilet requirement. 

Like wise  ‘change of use’ or ‘change of occupancy’ will trigger the need for a new building permit and compliance with current code.

Examples of types of use 

Assembly - place where unrelated people gather > restaurant, stadium, art gallery, gyms
Business - professions > doctors, hairdressers
Mercantile - things are sold, include grocery stores
Educational,
Factory & Industrial,
High Hazard,
Institutional,
Residential,
Storage,
Utility,
Historic - toilet requirement is often met by citing the availability of nearby toilets 

There are also sub-categories in these of ’type of use’ elements.  It appears unlikely that the construction done to change how a building is used could be done without a building permit and thus the need to meet current code.  Renovation, however, that does not change use or occupancy may not require updated toilet code although it likely triggers ADA toilet upgrade.

 

RESTROOM PRIVACY SUPPORT  

While commodes are typically housed in stalls, urinals are not.  Not all codes mandate privacy partitions between urinals.   Some men find this unsettling for a number of reasons.  A partition that is sufficiently high to block direct conversation can deter nefarious sexual advances

AR Position

Partitions should be required with dimensions sufficient to provide a site-line block from below the trunk and up to the face of the majority of expected users.  If stall requirements exist recommend the same height for urinal partitions.   In lieu of other substantive information suggest no less then 73 inches

IPC Position 

The IPC added partition code into the 2002 model.  It can be reviewed at page 6 proposal P9-04/05 for chapter 310.5  

310.5 (Supp) Urinal privacy partitions. Each urinal utilized by the public or employees shall occupy a separate area with walls or partitions to provide privacy. The construction of such walls or partitions shall incorporate waterproof, smooth, readily cleanable and nonabsorbent finish surfaces. The walls or partitions shall begin at a height not more than 12 inches (304.8 mm) from and extend not less than 60 inches (1524 mm) above the finished floor surface. The walls or partitions shall extend from the wall surface at each side of the urinal a minimum of 18 inches (457 mm) or to a point not less than 6 inches (152 mm) beyond the outermost front lip of the urinal measured from the finished back wall surface, whichever is greater.

Exceptions:
1. Urinal partitions shall not be required in a single occupant or unisex toilet room with a lockable door.
2. Urinals located in day care and child-care facilities and containing two or more urinals shall be permitted to have one urinal without partitions.

310.5 Urinal privacy. Each urinal utilized by the public or employees shall occupy a separate area with walls or partitions to provide privacy. The construction of such walls or partitions shall incorporate waterproof, smooth, readily cleanable and nonabsorbent finish surfaces. The walls or partitions shall begin at a height not more than 12 inches (304.8 mm) from and extend not less than 60 inches (1524 mm) above the finished floor surface. The walls or partitions shall extend from the wall surface at each side of the urinal a minimum of 18 inches (457 mm)or to a point not less than 6 inches (152 mm) beyond the outermost front lip of the urinal measured from the finished back wall surface, whichever is greater. Exception: Urinal partitions shall not be required in a single occupant or unisex toilet rooms with a lockable door. Commenter’s Reason: Floor action in Nashville was to approve this as submitted. The only stated reason for disapproval was that these requirements belong in the building code. This language and these similar requirements are currently in IPC Section 310.4 for water closets. If others see it fitting to also locate such text in the IBC, then approve this proposal and those folks can attempt to duplicate these requirements in the IBC later. The IPC water closet text on the same subject would need to do the same for consistency. This is a sanitation, and water conservation issue as well as privacy. It is not an uncommon situation where multiple urinals are located without privacy patricians that only one urinal will be used when multiple occupants enter at the same time. Thus the water closet will be used rather than the urinal, more water usage occurs and usually a soiled water closet seat is the result. This creates an insanitary condition and an unpleasant experience for the next user. This was proposed last code cycle and included testimony from “accessibility” experts that clearly stated this would not have an impact on the “accessibility” features of toilet rooms. Another issue brought up was that urinals manufactured with small side walls could be considered adequate. These type fixtures do not provide privacy; if a user stands close enough to gain the privacy aspect of these fixtures then splashing and sanitation become an issue. Urinals can be substituted for 67% of the required water closets. It is not reasonable for the code to allow two of the three users in a three-fixture toilet room absolutely no privacy when using such facilities. To keep up with potty parity and the like, the equivalent would be to now only require one out of three water closets in female toilet rooms to have privacy patricians. That would be ridiculous! The codes are designed so that males and females are entitled to, and provided, the same level of amenities, this includes privacy. Cost is a factor. In the past the code increased the number of fixtures required for females and this increased the cost of construction related to the space, labor and the materials. But, this is how codes evolve. Facts of reality identify problem areas and the codes address them, just as the fixture charts were determined to be deficient in the area of water closets for females for certain occupancies. Now, the voting membership has the opportunity to recognize and correct a deficiency in another area, privacy for males!

 

Source:  2004/2005 PROPOSED CHANGES TO THE INTERNATIONAL PLUMBING CODE   page 6 proposal P9-04/05 for chapter 310.5 

The UPC does not specify a requirement for urinal

"Each water closet shall occupy a separate compartment which shall be equipped with a door, door latch and clothes hook. The door and the walls or partitions between fixtures shall be sufficient to assure privacy."

 

NSPC - No available information 

 

 

GENDER / POTTY  PARITY  

Previous issues of the nation's model consensus code mandated an equal amount of toilet fixtures for both men and women.  Newer versions of the code will likely provide asymmetric recommendations that  increase the minimum required facilities for women. 

Go to our Potty Parity web page for more information

 

SUPPLEMENTARY/CONFLICTING STATE LEGISLATION  

Elected Officials sometimes introduce additional legislation, some of which appears to conflict with the model code adopted by their State.

Georgia  General Assembly of 2004 House Bill 1620 [did not pass]

To amend Article 1 of Chapter 16 of Title 50 of the Official Code of Georgia Annotated, relating to general provisions relative to public property, so as to provide standards for the number of women´s and men´s toilets in certain state, county, or city owned buildings and facilities; to provide for legislative findings; to provide for related matters; to repeal conflicting laws; and for other purposes.

SECTION 1.

The General Assembly recognizes that there are often long waiting periods for the use of restrooms in public buildings and facilities and that such waiting periods are much longer for women than for men due to gender differences in the need to use the restroom and anatomical differences between men and women. The General Assembly also recognizes that women often attend to small children in restrooms. Many states and localities have created laws to address the issue of insufficient restroom facilities for women in public buildings and facilities.


SECTION 2.

Article 1 of Chapter 16 of Title 50 of the Official Code of Georgia Annotated, relating to general provisions relative to public property, is amended by adding a new Code section to read as follows:
"50-16-21.
(a) Any women´s or men´s restroom constructed or installed on or after July 1, 2004, in a state, county, or city owned building or facility shall be in accordance with the Standard Building Code as provided by Part 2 of Article 1 of Chapter 2 of Title 8 and shall meet any applicable requirements of county boards of health.
(b) In addition to the requirements of subsection (a) of this Code section, any state, county, or city owned building or facility shall have a ratio of two toilets in each women´s restroom to every one toilet or urinal in a men´s restroom for restrooms that are constructed or installed on or after July 1, 2004."
Source: http://www.legis.state.ga.us/legis/2003_04/fulltext/hb1620.htm 

South Carolina 1997 Session 112 

H. 3250 --  Amend the code of laws of South Carolina, 1976 by adding Secton  39-41-295 so as to require a service station or convenience store selling gasoline and food or beverages to provide a public restroom and limit the application of this section to such service stations and convenience stores constructed on and after July 1, 1998.
Source:
http://www.lpitr.state.sc.us/sess112_1997-1998/hj97/01-16-97.hj.doc

 

Connecticut Public Health Code Section 19a-36 of the General Statutes

Toilet and Handwashing Facilities at Public Buildings, Places of Public Assembly, Places Dispensing Food and Beverages for Consumption on the Premises, and for the Patrons of Large Stores and Shopping Centers

19-13-B106. Toilet and handwashing facilities
Toilet and handwashing facilities accessible to the public and separated for each sex, shall be provided at new or extensively renovated public buildings, places of public assembly, places dispensing food and beverage for consumption on the premises, and for the patrons of large stores and shopping centers in accordance with the State of Connecticut Basic Building Code, except that this regulation shall not apply to establishments constructed or altered pursuant to plans and specifications approved or building permits issued prior to October 1, 1977.
Source: www.dph.state.ct.us/phc/docs/34_Toilet_and_Handwashing_F.doc                                   _______________________________________

How is compliance with 19-13-B106 enforced

 

Iowa Department of Public Health Memorandum to the State Board of Health

The Department of Public Health is required by statute to “establish, publish, and enforce a code of rules governing the installation of plumbing in cities and amend the same when deemed necessary.” Until 1982, the department maintained its own plumbing code. The lack of resources to maintain a full plumbing code and to publish it led to a decision to use a model code as the basis for the Iowa code; the Uniform Plumbing Code (UPC) was chosen.

Source: www.idph.state.ia.us/do/board_of_health_agendas/091201/plumbing_9_12_01.pdf

Maryland's Public Restroom Legislation

 

Loitering 

According to California Penal Code Section 647(d), 

 

 
Portland OR - I was at Wells Fargo in Portland, OR today to do some banking.  It was noonish, and I was enroute to home for lunch.  I made my deposit, and then asked to used the restroom, which I was told there wasn't a public restroom.  I am a customer and 8.5 months pregnant.  I left the bank in search of a bathroom, which took 15-20 minutes of unfamiliar territory, used the facilities of a public building, sat down for some lunch, and then back to my car, to find it had been towed away.   $200 later, I get my car back and no resolution from the bank for towing my car.   E.B.
Soruce: NARA Feedback dtd March 03, 2006 8:23 PM

 

 

                                                                                                                                                                         

American Restroom Association                                      
PO Box 65111                                                                        
Baltimore, MD 21209
202-747-6031 - Policy and Media queries 410-358-9007(FAX)

WARNING AND DISCLAIMER: The American Restroom Association (ARA) is formally incorporated in the State of Maryland and is a subsidiary of the International Paruresis Association  ARA is not qualified to provide legal advice. This web site contains non-vetted information that is un-official and for education only. There are no formal or financial agreements with any persons or entities cited. Some material is from copyrighted sources. This material is for education only and it must be source referenced.

Hit Counter